Windmill Cables | |||
EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable | HFEPR/HFEVA 0.6/1kV LSOH Screened Torsion Resistant Power Cable | Al Conductor EPR/XLEVA 0.6/1kV LSOH Power Cable 90℃ | more |
Windmill Cables
Al Conductor EPR/XLEVA 0.6/1KV LSOH Power Cable 90℃
Application
These durable, high temperature resistant LSOH cables are designed for wind turbines and dedicated for fixed
installation inside the tower.
Standards
IEC 60502-1
Construction
Conductor: Aluminium conductor, class 2 according to IEC 60228/EN 60228.
Insulation: Special cross-linked halogen free rubber EPR for high temperatures.
Sheath: Special cross-linked synthetic halogen free rubber EM8 (XLEVA). CPE can be offered upon request.
Technical Data
Rated Voltage Uo/U (Um):0.6/1kV
Operating Temperatures:-40℃~+ 90℃
Minimum Bending Radii:6×OD
Maximum Permissible Tensile Load:15N/mm²
Short-circuit Temperature:250℃
Flame Retardant:IEC 60332-1/ IEC 60332-3
Halogen Free:IEC 60754
Corrosive Gases:IEC 60754
Smoke Density:IEC 61034
Oil Resistant:Yes
Ozone Resistant:Yes
UV Resistant:Yes
Water Resistant:Yes
Dimensions and Weight
Construction | Nominal Overall Diameter | Nominal Weight |
---|---|---|
No. of cores×mm² | mm | kg/km |
1×150 | 22.5 | 640 |
1×185 | 25.0 | 770 |
1×240 | 27.8 | 980 |
1×300 | 30.5 | 1210 |
1×400 | 35.5 | 1550 |